易威奇 - IWAKI CHINA
Home > Products > Water Treatment Controllers

W100W Series
Cooling Tower / Boiler Controller

Plug into more options in water treatment control!


Three powerful control outputs make the Walchem W100W a more versatile, high value choice among entry level water treatment controllers.


The W100W series provide an economical and reliable way to keep your water treatment program under control.


Key Features:

Large display with icon based programming makes setup easy
Universal sensor input provides extraordinary flexibility; the same controller can be used with almost any type of sensor needed
Multiple language support allows simple setup no matter where your business takes you
Three control outputs allow the controller to be used in more places than other entry level models

Specification

Measurement Performance

  Range Resolution Accuracy

0.1 Cell Contacting Conductivity

0-3,000 μS/cm

0.1 μS/cm, 0.0001 mS/cm,
0.01 mS/m, 0.0001 S/m, 0.1 ppm

± 1% of reading

1.0 Cell Contacting Conductivity

0-30,000 μS/cm

1 μS/cm, 0.001 mS/cm, 0.1 mS/m, 0.0001 S/m, 1 ppm

± 1% of reading

10.0 Cell Contacting Conductivity

0-300,000 μS/cm

10 μS/cm, 0.01 mS/cm, 1 mS/m, 0.001 S/m, 10 ppm

± 1% of reading

Electrodeless Conductivity

500-12,000 μS/cm

1 μS/cm, 0.01 mS/cm, 0.1 mS/m, 0.001 S/m, 1 ppm

± 1% of reading

3,000-40,000 μS/cm

1 μS/cm, 0.01 mS/cm, 0.1 mS/m, 0.001 S/m, 1 ppm

± 1% of reading

10,000-150,000 μS/cm

10 μS/cm, 0.1 mS/cm, 1 mS/m, 0.01 S/m, 10 ppm

± 1% of reading

50,000-500,000 μS/cm

10 μS/cm, 0.1 mS/cm, 1 mS/m, 0.01 S/m, 10 ppm

± 1% of reading

200,000-2,000,000 μS/cm

100 μS/cm, 0.1 mS/cm, 1 mS/m, 0.1 S/m, 100 ppm

± 1% of reading

Temperature

23 to 500°F
(-5 to 260°C)

0.1°F (0.1°C)

± 1% of reading within range

 

Mechanical (Controller)

Enclosure

Polycarbonate

Enclosure Rating

NEMA 4X (IP65)

Display

128 x 64 graphic backlit display

Ambient Temperature

-4 to 131°F (-20 to 55°C)

Shipping Temperature

-4 to 176°F (-20 to 80°C)

Shipping weight

22 lbs (10 kg) (approximately) varies with model

 

Flowrate(L/min)
Max. Head(m)
Max. Discharge Pressure(MPa)
Min. Media Temp.(°C)
Max. Media Temp.(°C)
Water Controller Function