Take Control Now and Connect with the Best!
The W600 series provides reliable, flexible and powerful control for your water treatment program.
Key Features:
• Large touchscreen display with icon based programming makes setup easy
• Universal sensor input provides extraordinary flexibility; the same controller can be used with almost any type of sensor needed
• Optional dual analog (4-20 mA) input for Fluorometers or nearly any other process value
• Multiple language support allows simple setup no matter where your business takes you
• Six control outputs allow the controller to be used in more applications
• Economical wall-mount package for easy installation
• On-screen graphing of sensor values and control output status
• Complete flexibility in the function of each relay:
• On/Off Setpoint
• Time Proportional Control
• Pulse Proportional Control (when purchased with solid-state relays)
• In-Range or Out-of-Range activation
• Probe wash
• Timer-based activation
• Activation based upon the state of a contact closure
• Timed activation triggered by Water Contactor / Paddlewheel flow meter’s accumulated total flow
• Activate with another output
• Activate as a percent of another output’s on-time
• For Cooling Tower and Boiler applications:
• Biocide Timer
• Boiler blowdown on conductivity using intermittent sampling
• Datalogging
• Ethernet option for remote access via the Internet or LAN
Specification
Measurement Preformance
Range |
Resolution |
Accuracy |
|
Contacting Conductivity |
0 ~ 3,000 μS/cm |
0.1 μS/cm, 0.0001 mS/cm, 0.01 mS/m, |
± 1% of Reading |
0 ~ 30,000 μS/cm |
1 μS/cm, 0.001 mS/cm, 0.1 mS/m, |
± 1% of Reading |
|
0 ~ 300,000 μS/cm |
10 μS/cm, 0.01 mS/cm, 1 mS/m, |
± 1% of Reading |
|
Electroless Conductivity |
500 ~ 12,000 μS/cm |
1 μS/cm, 0.01 mS/cm, 0.1 mS/m, |
± 1% of Reading |
3,000 ~ 40,000 μS/cm |
1 μS/cm, 0.01 mS/cm, 0.1 mS/m, |
± 1% of Reading |
|
10,000 ~ 150,000 μS/cm |
10 μS/cm, 0.1 mS/cm, 1 mS/m, |
± 1% of Reading |
|
50,000 ~ 500,000 μS/cm |
10 μS/cm, 0.1 mS/cm, 1 mS/m, |
± 1% of Reading |
|
200,000 ~ 2,000,000 μS/cm |
100 μS/cm, 0.1 mS/cm, 1 mS/m, |
± 1% of Reading |
|
Temperature |
23 ~ 500°F |
0.1°F (0.1°C) |
± 1% of Reading within Range |
pH | -2 ~ 16 pH unit | 0.01 pH unit | ± 0.01% of Reading |
ORP | -1,500 ~ 1500 mV | 0.01 mV | ± 0.01% of Reading |
Disinfestion Sensor |
-2,000 ~ 1,500 mV | 0.01 mV | ± 1mV |
0~2 ppm ~ 0~20,000 ppm | Varies with range and slope |
Varies with range and slope |
Mechanical (Controller)
Enclosure Material |
Polycarbonate |
Enclosure Rating |
NEMA 4X (IP65) |
Display |
320 x 240 pixel monochrome backlit display with touch screen |
Ambient Temperature |
-4 ~ 131°F (-20 ~ 55°C) |
Storage Temperature |
-4 ~ 176°F (-20 ~ 80°C) |